14.2 START/STOP AND SPEED CONTROL
14.2.1 REMOTE MODE SELECTION
The REMOTE mode can be selected by one of two methods:
1. Program Parameter 30 - CONTROL to REMOTE, or:
2. ProgramCONTROLtoBOTH,settheTB-13AorTB-13Cfunction(seeParameter47or49)to
LOCALSELECT,andDONOTmakeacontact closurebetweenTB-13A orTB-13CandTB-2
(makingthecontactclosurewillselectLOCALmode).
IfCONTROLissettoLOCAL,TB-1isdisabledandCANNOTbeusedasaSTOPswitch!
Incorrect use of TB-1 may result in damage to equipment and/or injury to personnel! See
Parameter 30 - CONTROL.
STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersare
resetto factorydefaults! Thedrive mustbereprogrammedafteraRESETinordertoinsure
properoperation(seeParameter65-PROGRAM).
FAILURETODOSOMAYRESULTINDAMAGETOEQUIPMENTAND/ORINJURY
TOPERSONNEL!
14.2.2 TWO-WIRE START/STOP CONTROL
A two-wire start/stop circuit can be accomplished by one of three methods on the MICRO Series drive.
Follow the appropriate procedure listed below:
FORWARD ROTATION ONLY
1. SelectREMOTEmode(see14.2.1).
2. ConnectajumperbetweenTB-12AandTB-2toprovideapermanentSTARTcommandtothedrive.
3. Wire a normally open maintained contact between TB-1 and TB-2. Closing this contact will RUN
the drive and opening this contact will STOP the drive.
FORWARD and REVERSE ROTATION
1. SelectREMOTEmode(see14.2.1).
2. Program Parameter 27 - ROTATION to FWD & REV to allow rotation in both directions.
3. Program Parameter 49 - TB13C to START REVERSE. This will force TB-12A to act as START
FORWARD.
4. Select the desired rotation by closing the appropriate terminal (TB-12A for forward, or TB-13C for
reverse)toTB-2.Thiscanbedonewithatoggleswitchorequivalentcircuit.
5. Wire a normally open maintained contact between TB-1 and TB-2. Close this contact to RUN the
drive, and open this contact to STOP the drive.
35