SPEEDMASTER®Micro Series CompactInverters Installation and Operation ManualA Regal Brand

Seite 2

84.2 TYPE 1 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac and 60 HP at 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N C P Q S

Seite 3 - TABLE OF CONTENTS

94.3 WASHGUARD NEMA 4/12, 12, & 4X* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. Slo

Seite 4 - TABLE OF CONTENTS (cont’d.)

10WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q

Seite 5 - IMPORTANT NOTICE

114.4 TYPE 12 DIMENSIONS FOR MODELS RATED ABOVE 30 HP AT 240/200 Vac AND 60 HP AT 590/480/400 Vac HP INPUT (kW) VOLTAGE MODEL H W D N P Q

Seite 6 - 1.0 GENERAL

12* = NEMA 12 Only** = NEMA 4XOthers are NEMA 4/12WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF

Seite 7

135.0 MICRO SERIES RATINGS115/230 & 230V (SINGLE PHASE) VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (120/240 Vac, 50-60 Hz) (0-230 Vac)

Seite 8 - 4.0 MICRO SERIES DIMENSIONS

14230 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (200/240 Vac, 50-60 Hz) (0-200/230 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Seite 9

15460 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (400/480 Vac, 50-60 Hz) (0-400/460 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Seite 10 - Small holes = 1.13”

16575 VOLT MICRO SERIES RATINGS MODEL INPUT OUTPUT (480/590 Vac, 50-60 Hz) (0-460/575 Vac) FOR MOTORS NOMINAL NOMINAL CATALOG RATED

Seite 11 - Others are NEMA 4/12

6.0 THEORY6.1 DESCRIPTION OF AC MOTOR OPERATION ThreephaseACmotorsarecomprisedoftwomajorcomponents,thestatorandtherotor.Thestatoris

Seite 13

 Ifthefrequencyappliedtothemotorisincreasedwhilethevoltageremainsconstant,torquecapabilitywilldecreaseasspeedincreases.Thiswill

Seite 14

 “Variabletorque”referstothefactthatthetorquerequiredvarieswiththesquareofthespeed.Also,the horsepower required varies with th

Seite 15 - 5.0 MICRO SERIES RATINGS

6.2.3 MICRO SERIES INPUTS AND OUTPUTS Thedrivehas two analog inputs (0-10 VDC and 4-20 mA) that can beused for speed reference, PI

Seite 16 - OTHERS ARE NEMA 1 ENCLOSURE

The following describes the possible relay output settings: NONE This setting disables the relay output. RUN The relay energizes when the dri

Seite 17

7.0 INSTALLATION DRIVESMUSTNOTBEINSTALLEDWHERESUBJECTEDTO ADVERSE ENVI- RONMENTAL CONDITIONS! DRIVES MUST NOT BE INSTALLED WHERESUBJ

Seite 18

7.1 INSTALLATION AFTER A LONG PERIOD OF STORAGE Severe damage to the drive can result if it is operated after a long period of storage or inactivity

Seite 19 - 6.0 THEORY

8.0 INPUT AC REQUIREMENTS Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain

Seite 20 - % SPEED

9.0 VOLTAGE SELECTION9.1 INPUT VOLTAGE RATINGS 115/230 Volt MICRO Seriesdrivesareratedfor240/120Vac,50-60Hzinput.Thedrivewillfunction

Seite 21

11.0 MICRO SERIES POWER WIRING DIAGRAM Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive will result.

Seite 22

12.0 INITIAL POWER UP Hazardofelectricalshock.Disconnectincomingpowerandwaitthreeminutesbeforeservicingthe drive. Capacitors retain cha

Seite 23

TABLE OF CONTENTS1.0 GENERAL ... 4 PRODUCT CHANGES ...

Seite 24 - 7.0 INSTALLATION

 3. If the motor is rotating in the wrong direction, press the “STOP” key, remove power from the drive, wait three minutes for the

Seite 25

13.2 MICRO SERIES DISPLAY The following describes the possible display configurations for the SPEEDMASTER MICRO Series drive.13.2.1 MICRO SERIES DI

Seite 26 - 8.0 INPUT AC REQUIREMENTS

30 The following table shows the possible DRIVE STATUS indications that can appear on the drive display:DRIVE STATUS TABLE DISPLAY DESCRIPTION ST

Seite 27 - 10.0 POWER WIRING

13.2.2 MICRO SERIES DISPLAY IN RUN MODE WhenthedriveisintheRUNmode,thedefaultdisplaywilllooklikethis: AsintheSTOPmode,theENTER

Seite 28

3213.2.3 MICRO SERIES DISPLAY IN FAULT MODE When the drive trips on a fault, the display will automatically change to the FAULT display, which indic

Seite 29 - 12.0 INITIAL POWER UP

33 Thetable belowshowsthe possibleSPEEDREFERENCESOURCEindications fortheauxiliarystatus display:SPEED REFERENCE TABLE DISPLAY DESCRI

Seite 30 - 13.0 KEYPAD CONTROL

14.0 CONTROL WIRING14.1 GENERAL14.1.1 KEYPAD CONTROL Thedrivecanbecontrolledbythekeypadorbycontroldeviceswiredtotheterminalstrip.T

Seite 31

14.2 START/STOP AND SPEED CONTROL14.2.1 REMOTE MODE SELECTION The REMOTE mode can be selected by one of two methods: 1. Program Parameter 30 - CO

Seite 32

14.2.3 ALTERNATE TWO-WIRE START/STOP CONTROL METHOD  This method requires TB-13C to be set for RUN REVERSE, which will disable TB-1 a

Seite 33

14.2.4 THREE-WIRE START/STOP CONTROL A three-wire start/stop circuit can be accomplished by one of two methods on the MICRO Series drive. Follow the

Seite 34

TABLE OF CONTENTS (cont’d.)19.0 MICRO SERIES PID SET POINT CONTROL ... 77 FEEDBACK DEVICES . . . . . . . . . . . . . . . .

Seite 35

14.2.5 SPEED REFERENCE SIGNALS Thedriveallowsforthreeanalogspeedreferenceinputs:aspeedpotentiometer(10,000Ohm),0-10VDC,or 4-20 mA.

Seite 36 - 14.0 CONTROL WIRING

 JOG TheJOGfunctiononlyworkswhenthedriveisinREMOTEmode,andonlywhenthedriveisinaSTOPcondition.TB-13Bcanbeprogrammedforeith

Seite 37

15.0 MICRO SERIES CONTROL WIRING DIAGRAMS15.1 MICRO SERIES TERMINAL STRIP Shown below is the terminal strip on the main control board, along with a

Seite 38

15.2 TWO-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical two-wire start/stop control scheme, using one maintained contact(s

Seite 39

15.3 THREE-WIRE START/STOP CONTROL Shown below is the wiring diagram for a typical three-wire start/stop control scheme, using momentary contacts(

Seite 40

15.4 SPEED POT AND PRESET SPEED CONTROL ShownbelowisthewiringdiagramforacontrolschemethatutilizesaspeedpotandPRESETSPEEDSforspeed

Seite 41

16.0 PROGRAMMING THE MICRO SERIES DRIVE16.1 PROGRAMMING THE PARAMETERS The MICRO Series keypad serves two purposes: operating the drive w

Seite 42

Once the correct password is entered, the PROGRAM mode will be entered and the first parameter will be displayed, which is Parameter 0 - LINE VOLTS.

Seite 43

16.2 PARAMETER ACCESS USING SPEED DIAL SPEED DIAL is used to access parameters quickly using the parameter number. Once accessed, the

Seite 44

4717.0 PARAMETER MENUNOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE

Seite 45

3IMPORTANT NOTICEThe following , and information is supplied to you for your protection and to provi

Seite 46 - 20.00 HZ

48NOTE 1: REFER TO SECTION 18.0 - DESCRIPTION OF PARAMETERS.NOTE2:MAXLIMITIS650HzONUNITSWITHHIGHFREQUENCYSOFTWARE.NOTE3:IFLINEVOLTSIS

Seite 47

49PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT  43 @TB10A 0.00-360.0HZ(NOTE2) 60.00Hz 44 TB10B O

Seite 48

50PARAMETER MENU PARAM. PARAMETER RANGE OF FACTORY NUMBER NAME ADJUSTMENT DEFAULT 65 PROGRAM MAINTAIN, RESET 60,   RESET50(NOTE4) RES

Seite 49 - 17.0 PARAMETER MENU

5118.0 DESCRIPTION OF PARAMETERS 0 LINE VOLTS (LINEVOLTAGE) This parameter calibrates the drive for the correct input voltage, and can be set

Seite 50

1-4 SPEED #1-#4 (PRESETSPEEDS#1,#2,#3,AND#4) PRESET SPEEDS are only active when the drive is in AUTO mode, and are activated via contact clo

Seite 51

Example:Thecriticalfrequencyis21Hz,andabandwidthof2Hzisdesired.Therefore,setSKIP#1to20HzandsetSKIPBANDWIDTHto2Hz.Thisr

Seite 52

54 NOTE 1: 240/120 Vac units have the same limits as 240/200 Vac units. NOTE 2: The parameter value can be set below the minimum value shown, but th

Seite 53

11 MAX FRQ (MAXIMUMFREQUENCY) Thisparameterdefinestheupperlimitofthedrive’sspeedrange.MAXFRQisusedinconjunctionwithMINFRQ(Par

Seite 54

14 DYN BRAK (DYNAMICBRAKE) This parameter enables the dynamic braking circuit. Set this parameter to ON only if the optional dyna

Seite 55

 The“speed-compensated”thermaloverloadcircuitoffersadditionalprotectionfromhighloadconditionsatlowspeeds,wheremotorcoolingisoften

Seite 56

1.0 GENERAL1.1 This manual covers the LEESON MICRO Series Inverters.1.2 PRODUCT CHANGES LEESON Electric reserves the right to discontinue or

Seite 57

18 BASE (BASEFREQUENCY) The BASE FREQUENCY determine the V/Hz ratio by setting the frequency at which the drive will output full

Seite 58

20 AC BOOST (ACBOOST) AC BOOST is similar to FX BOOST, but is only active when the drive is accelerating. During acceleration, theoutputvoltage

Seite 59 - OUTPUT CURRENT (%)

22 TORQUE (TORQUECURVESELECTION) ThisparameterisusedtoselectwhethertheoutputofthedrivefollowsaconstantorvariableV/Hzcurve.The

Seite 60

25 START (STARTMODE)  Automaticstartofequipmentmayresultindamagetoequipmentand/orinjurytopersonnel!Automaticstartshouldonlybe

Seite 61 - OUTPUT VOLTAGE (%)

27 ROTATION (ROTATIONDIRECTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein

Seite 62

29 MANUAL (MANUAL) This parameter selects the speed reference source when the drive is set for MANUAL speed control (seeparameter28 - AUTO/MAN

Seite 63

33 SPEED DP (SPEEDDECIMALPOINT) This parameter is used to move the decimal point location in the speed display. This parameter will not have any

Seite 64

Example:SLEEP THRESHOLD isset to15Hz andSLEEP DELAYisset to60seconds. Ifthe drive operates below 15Hzfor60 seconds, the dr

Seite 65

41 AIN FLTR (ANALOGINPUTFILTER) Thisparameteradjuststhefilterontheanaloginputterminals(TB-5AandTB-5B)toreducetheeffectofanyel

Seite 66

47 TB13A (TB-13AINPUTFUNCTION) This parameter is used to select the function of terminal TB-13A. Closing TB-13A to TB-2 activates the TB-13

Seite 67

2.0 MICRO SERIES SPECIFICATIONS Storage Temperature -20° to 70° C Ambient Operating Temperature Chassis -10° to 55° C  (With2.5and8kHZcar

Seite 68

49 TB13C  (TB-13CINPUTFUNCTION) If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a STOPswitch!Thisistruein

Seite 69

50 TB13D  (TB-13DFUNCTION)  STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaults!The

Seite 70

SPEED #3 value. See Parameter 3 - SPEED #3 in Section 18.0 - DESCRIPTION OF PARAMETERS, ILIMIT  CURRENTLIMIT-Therelayenergizeswhenthedrive

Seite 71

71 SPD=0HZ Therelayenergizeswhenthereisnooutputtothemotor,foranyreason,suchas:drive    isinSTOPmode,driveisinRUNmode

Seite 72

NOTE 2: If a RESET command (Parameter 65 - PROGRAM) is issued through the serial link, this parameter will not default back to

Seite 73

65 PROGRAM (PROGRAMFACTORYDEFAULTS) STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersareresettofactory defaul

Seite 74

70 PID MODE (PIDMODESELECT) This parameter activates the PID function, and selects whether the PID control will be direct or reverse acting.

Seite 75

NOTE:Ifareverseactingfeedbackdeviceisbeingused,FB@MINshouldbesettothemaximumprocessvariable value, and FB @ MAX should be set to

Seite 76

relayoropen-collectoroutputwillde-energize,whichopensthestartcontactandstopsthedrive.WhenthesignalisequaltoorgreaterthantheMI

Seite 77

19.0 MICRO SERIES PID SET POINT CONTROL PID Set point Control allows the MICRO Series Control to maintain a process set point, such as PSI orCFM,w

Seite 78

64.0 MICRO SERIES DIMENSIONS4.1 TYPE 1 ENCLOSEDWRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ≤ 7

Seite 79

 Forareverseactingtransducer,setParameter75-FB@MINtothemaximumprocessvariablefeedbackvalue,andsetParameter76-FB@MAXtothe

Seite 80

eachtype,sothesametypeofsignalcannotbeusedfortransducerfeedbackandsetpointreference.For example,a4-20mAsignalfromatransducer

Seite 81

When the drive is in PID mode, the DRIVE STATUS portion of the display will indicate actual output frequency(inHertz)insteadofRUN,andtherig

Seite 82

8120.0 TROUBLESHOOTING The table below lists the fault conditions that will cause the drive to shut down, as well as some possible causes. Please con

Seite 83 - 20.0 TROUBLESHOOTING

82FAULT MESSAGES FAULT DESCRIPTION POSSIBLE CAUSES EXTERNAL Externalfault:TB-13Disopenorclosed ChecksettingofParameter to TB-2, depe

Seite 84

8321.0 USER SETTING RECORDPARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 0 LINE VOLTS AUTO 1

Seite 85 - 21.0 USER SETTING RECORD

84PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 20 AC BOOST .0% 21 SLIP CMP .0% 22 TORQUE

Seite 86

8585PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 42 TB10A OUT NONE 43 @TB10A 60.00Hz 44

Seite 87

86PARAMETER MENU: USER SETTING RECORD PARAM. PARAMETER FACTORY USER NUMBER NAME DEFAULT SETTING 74 PID FB TB-5A 75 FB @ MIN 0.00% 76 FB

Seite 88

EC DECLARATION OF CONFORMITYWe,LEESON Electric1051 Cheyenne AvenueGrafton, Wisconsin 53024 U.S.A.declareundersoleresponsibilitythatthefollowing

Seite 89 - LEESON Electric

7WRDHQQPNConduit Holes:S Dia.0.88" Dia.S Dia.TDia. SlotMounting Tab DetailWUV1.00"RIF W ʺ 7.86"T = 0.20"U = 0.34"V = 0.19&q

Seite 92 - A Regal Brand

A Regal BrandLEESON ElectricGrafton, Wisconsin 53024 U.S.A.PH: 262-377-8810FAX: 262-377-9025www.leeson.comREGAL BELOIT CANADAMississauga (Toronto), On