The following describes the possible relay output settings:
NONE This setting disables the relay output.
RUN The relay energizes when the drive is given a START command, and remains
energized until: a STOP command is given and the output frequency has
deceleratedto0.5Hz,thedrivehas“tripped”,ortheinputvoltageisremoved.
Note that this relay indicates only that the drive is in the RUN mode. It does not
necessarily indicate that the motor is turning.
FAULT The relay energizes when input voltage is applied to the drive and remains
energizeduntilthedrive“trips”intoafaultcondition,orinputvoltageisremoved.
/FAULT INVERSE FAULT - The relay energizes when the drive trips into a fault
condition,andremainsenergizeduntilthefaultconditioniscleared.
LOCK FAULT LOCKOUT - This relay is used when the drive is programmed to
automaticallyrestartafterafault.Therelayenergizeswheninputvoltageisapplied
tothedriveandremainsenergizeduntilthedrivehasfaultedandunsuccessfully
attempted five restarts, or input voltage is removed.
@SPEED AT SPEED - The relay energizes when the drive reaches the commanded
frequency.Toavoida“chattering”relay(constantlyenergizingandde-energizing),
due to small fluctuations in speed. the relay will change states only when the
actualspeedandthespeedsetpointdifferby3Hz.
ABOVE#3 The relay energizes when the output frequency of the drive exceeds the value
corresponding to the SPEED #3 value, and de-energizes when the output
frequencyreturnstoavaluelowerthantheSPEED#3value.SeeParameter3-
SPEED #3 in Section 18.0 - DESCRIPTION OF PARAMETERS.
ILIMIT CURRENT LIMIT - The relay energizes when the drive is operating in
currentlimit.Oncethecurrentlimitrelayisenergized,itremainsenergizedfor
a minimum of 500ms, regardless of whether the drive is still in current limit. At
theendofthe500msinterval,therelaywillde-energizeifthedriveisnolongerin
current limit. See Parameter 16 - CURRENT in Section 18.0 - DESCRIPTION
OF PARAMETERS.
AUT/MAN The relay energizes when the drive is in the AUTOMATIC mode, and
de-energizes in the MANUAL mode. Refer to Section 14.2.6 - SPEED
REFERENCE SELECTION.