“Variabletorque”referstothefactthatthetorquerequiredvarieswiththesquareofthespeed.Also,the
horsepower required varies with the cube of the speed, resulting in a large reduction in horsepower for
even a small reduction in speed. It is easily seen that substantial energy savings can be achieved by reducing
thespeedofafanorpump.Forexample,reducingthespeedto50%resultsina50HPmotorhavingto
produceonly12.5%ofratedhorsepower,or6.25HP.Variabletorquedrivesusuallyhavealowoverload
capacity (110%-120% for 60 seconds), becausevariabletorque applications rarely experience overload
conditions.To optimizeefficiencyand energysavings, variabletorquedrives areusually programmedto
followavariableV/Hzratio.
Theterm“constanttorque”isnotentirelyaccurateintermsoftheactualtorquerequiredforanapplication.
Manyconstanttorqueapplicationshavereciprocatingloads,suchasvibratingconveyorsandpunchpresses,
wheretherotationalmotionofthemotorisbeingconvertedtoalinearmotion.Insuchcases,thetorque
requiredcanvarygreatlyatdifferentpointsinthecycle.Forconstanttorqueloads,thisfluctuationintorque
isnota directfunctionof speed, asit is withavariable torqueload.As a result,constant torque drives
typically have a high overload rating (150% for 60 seconds) in order to handle the higher peak torque
demands.Toachievemaximumtorque,constanttorquedrivesfollowaconstantV/Hzratio.
MICROSeriesproductlineshavefulloverloadcapacity(150%for60seconds,180%for30seconds),so
thateitheronecanbeusedforeithertypeofapplication.TheV/Hzratiocanalsobechangedtooptimize
performance for either type of application.
6.2 DRIVE FUNCTION DESCRIPTION
TheMICROSeriesisa16bitmicroprocessorbased,keypadprogrammable,variablespeedACmotordrive.
Therearefourmajorsections;aninputdiodebridgeandafilter,apowerboard,acontrolboard,andan
output intelligent power module.
6.2.1 DRIVE OPERATION
Incoming AC line voltage is converted to a pulsating DC voltage by the input diode bridge. The DC
voltage is supplied to the bus filter capacitors through a charge circuit which limits inrush current to the
capacitors during power-up. The pulsating DC voltage is filtered by the bus capacitors which reduces
theripplelevel. ThefilteredDCvoltageenterstheinvertersectionofthe drive,composedofsixoutput
intelligentinsulatedgate bi-polartransistors(IGBT’s)whichmakeupthethreeoutputlegs ofthedrive.
Each leg has one intelligent IGBT connected to the positive bus voltage and one connected to the negative
bus voltage. Alternately switching on each leg, the intelligent IGBT produces an alternating voltage on each
ofthecorrespondingmotorwindings.ByswitchingeachoutputintelligentIGBTataveryhighfrequency
(knownasthecarrierfrequency)forvaryingtimeintervals,theinverterisabletoproduceasmooth,three
phase,sinusoidaloutputcurrentwavewhichoptimizesmotorperformance.
6.2.2 CIRCUIT DESCRIPTION
Thecontrolsection consistsof acontrol boardwitha16bitmicroprocessor,keypadanddisplay. Drive
programming is accomplished via the keypad or the serial communications port. During operation the
drivecanbecontrolledviathekeypad,bycontroldeviceswiredtothecontrolterminalstrip,orbytheserial
communications port. The Power Board contains the control and protection circuits which govern the
sixoutputIGBT’s.ThePowerBoardalsocontainsachargingcircuitforthebusfiltercapacitors,amotor
currentfeedback circuit,avoltagefeedbackcircuit, anda faultsignal circuit.Thedrive hasseveral built
in protection circuits. These include phase-to-phase and phase-to ground short circuit protection, high
andlowlinevoltageprotection,protectionagainstexcessiveambienttemperature,andprotectionagainst
continuousexcessiveoutputcurrent.Activationofanyofthesecircuitswillcausethedrivetoshutdown
in a fault condition.